WinCC Unified - Clamping tag value
In my previous post, I shared the importance of setting tag limits to prevent bad data from causing issues in SCADA systems. Now, let's talk about another essential safeguard — clamping values.
Clamping vs. Tag Limits
While both clamping and tag limits help control data quality, they serve different purposes:
- 
Tag limits: Used to filter out and reject values that exceed a predefined range, preventing them from being processed at all. 
- 
Clamping: Adjusts out-of-range values to stay within acceptable limits, ensuring the system continues to function without interruption. 
Steps to implement Clamping in WinCC Unified
- 
Create Data, Lower and Upper Bound Tags- Open the Tag Table and create a data tag (e.g., Data_Integer_Value), a lower bound tag and an upper bound tag
- Set the lower and upper bound tags with their respective Start value(e.g. upper bound = 100, lower bound = 0)  
 
- Open the Tag Table and create a data tag (e.g., 
- 
Link Data Tag to a Screen Element- Add a new Screen.
- In the new screen, add an IO Field element.
- Link the Process Value of the IO Field to the tag Data_Integer_Value.  
 
- 
Define Upper and Lower Clamping Function- Add a Input finishedevent with the code below.
 
- Add a 
export function IO_field_1_OnInputFinished(item, value) { let tag = Tags("Data_Integer_Value"); let lower = Tags("lower_bound").Read(); let upper = Tags("upper_bound").Read(); let result; if(value < lower){ result = lower; } else if (value > upper){ result = upper; } else{ result = value; } tag.Write(result); return result; }

 
 
 
 

 .
. 